Auxiliary Transformer

Auxiliary transformer saving cost and enviromental-friendly

In areas where an earth point is not readily available or difficult to acquire, a neutral point can be created using an earthing transformer. Earthing transformers, incorporate a zig-zag (interstar) winding feature that is used to achieve the required zero phase impedance stage, providing the desired neutral earthing conditions. Additionally, auxiliary windings are often provided according to auxiliary power supply requirements.

Auxiliary Transformer

Related product parameters

Technical Specifications  
Type oil immersed
Power up to 2000kva
Voltage up to 36KV
Current 3000A
Duty seconds 10/30/60 or others
Cooling method ONAN, AF
Frequency 50/60Hz
Standard IEC60076
Vertor group ZNyn1
Installnation indoor /outdoor
Ambient Temperature -30 +55 ℃

FACTORY TEST

For each transformer are prepared and issued a test report, in accordance with IEC 60076. except for routine tests, we also offer type tests and specialized tests to meet all customer requirements. We make what matters work for our customers in a safe and reliable way.

Routine test

  •  Measurement of winding resistance
  •  Measurement of voltage ratio and check of phase displacement
  •  Measurement of short-circuit impedance and loss
  •  Measurement of no-load loss and current
  •  Dielectric routine tests
  •  Tests on on-load tap-changers, where appropriate
  •  Leak testing with pressure for liquid-immersed transformers(tightness test)
  •  Tightness tests and pressure tests for tanks for gas-filled transformers
  •  Check of the ratio and polarity of built-in current transformers
  •  Check of core and frame insulation for liquid immersed transformers with core or frame insulation

 Type test

  •  Temperature-rise type test
  •  Dielectric type tests
  •  Determination of sound level for each method of cooling for which a guaranteed sound level is specified
  •  Measurement of the power taken by the fan and liquid pump motors
  •  Measurement of no-load loss and current at 90% and 110% of rated voltage

 Special Test

  •  Dielectric special tests
  •  Winding hot-spot temperature-rise measurement
  •  Determination of capacitances windings-to-earth, and between windings
  •  Measurement of dissipation factor(tanδ) of the insulation system capacitances
  •  Determination of transient voltage transfer characteristics
  •  Measurement of zero-sequence impedance(s) on three-phase transformers
  •  Short-circuit withstand test
  •  Measurement of d.c. insulation resistance each winding to earth and between windings
  •  Vacuum deflection test on liquid immersed transformers
  •  Pressure deflection test on liquid immersed transformers
  •  Vacuum tightness test on site on liquid immersed transformers