What is the permissible overload percent for oil-immersed transformers?

2025-02-06

Introduction

In practical applications, oil-immersed transformers are often subjected to temporary overload conditions due to fluctuations in power demand. Understanding the permissible overload capacity is crucial for maintaining reliability, extending service life, and avoiding thermal degradation. The allowable overload percentage depends on various factors such as insulation class, cooling method, and operational environment.  

 

Standard Overload Limits

Industry standards such as IEEE C57.91-2011 and IEC 60076-7 define permissible overload percentages based on transformer insulation class and cooling conditions. The general guidelines are:

Normal Short-Term Overload Limits:

These limits ensure that the transformer does not exceed its designed thermal capabilities under momentary peak loads.

Emergency Overload Conditions:

Previous continuous loading oil temperature duration(min) of overloading for specific levels of overloading
% of rated power 10% Min 20% Min 30% Min 40% Min 50% Min
50 55 180 90 60 30 15
75 68 120 60 30 15 8
90 78 60 25 15 8 4

 

Factors Influencing Overload Capability

Several factors influence the permissible overload of an oil-immersed transformer:

1. Cooling Method (ONAN, ONAF, OFAF, OFWF, etc.)

Forced cooling mechanisms such as ONAF (Oil Natural Air Forced) or OFAF (Oil Forced Air Forced) enhance heat dissipation, allowing higher overload tolerances.

2. Ambient Temperature and Load Profile

Higher ambient temperatures reduce thermal margins, lowering permissible overload levels. A lower ambient temperature may allow slight extensions of overload duration.

3. Insulation Aging and Hot-Spot Temperature

Prolonged overload operation accelerates insulation aging due to excessive hot-spot temperatures. IEC standards recommend keeping the hot-spot temperature below 110°C for longevity.

4. Duration of Overload

Short-duration overloads (minutes to hours) are generally acceptable within the recommended limits. Continuous overload operation, however, leads to increased thermal stress, ultimately reducing transformer lifespan.

 

Engineering Considerations for Overloading

When planning to operate a transformer under overload conditions, engineers must:

  1. Assess cooling system efficiency – Verify that cooling fans and radiators function properly to enhance heat dissipation.

  2. Monitor oil and winding temperatures – Use thermal sensors and real-time monitoring to prevent excessive temperature rise.

  3. Perform load flow analysis – Ensure that system protection and relay settings are adjusted for safe overload operation.

  4. Consult manufacturer guidelines – Always refer to OEM specifications for transformer-specific overload limits and thermal models.

 

Conclusion

Permissible overload percentages for oil-immersed transformers depend on design factors, cooling effectiveness, and insulation aging considerations. While temporary overloads are manageable within recommended limits, continuous overloading must be carefully evaluated to prevent accelerated wear and potential failures. Engineers should implement monitoring and cooling strategies to optimize transformer performance while ensuring long-term reliability.

For custom overload assessments tailored to specific transformer designs, consult Varelen’s engineering team for expert recommendations and solutions.